Declaration of Conformity

Specific Conditions of Use (X):
1. Precautions shall be taken to minimize the risk from electrostatic
discharges and propagating brush discharges. Only clean with a
damp cloth.
2. The display glass shall be positioned in such a way as to minimize the
risk of mechanical impact.
3. The transmitter head shall only be rotated on top of the antenna in
the absence of an explosive atmosphere.
4. The equipment shall only be used in an area of at least pollution
degree 2, as defined in IEC 60664-1.
5. Cable entries must be used which maintain the ingress protection of
the enclosure to at least IP65. To maintain the ingress protection
ratings, Covers and Sensor Module to be fully tightened and PTFE
tape or pipe dope is required for cable entries and blanking plugs.
See Instruction Manual on application requirements.
6. The applicable temperature class versus the ambient temperature
range and process temperature range of the equipment is as follows:
Temperature class Ambient temperature
range
Process temperature
range
T2 -55 °C ≤ Ta ≤ +43 °C -55 °C to +200 °C
T3 -55 °C ≤ Ta ≤ +53 °C -55 °C to +195 °C
T4 -55 °C ≤ Ta ≤ +70 °C -55 °C to +130 °C
1.14 Additional certifications
1.14.1 QT Safety-certified to IEC 61508:2010 with certificate of FMEDA data
Certificate
Pending
1.14.2 Suitable for intended use
Compliant with NAMUR NE 95:2013, “Basic Principles of Homologation”
(Pending)
1.14.3 U1 Overfill prevention
Certificate
Pending
Application
TÜV tested and approved by DIBt for overfill prevention
according to the German WHG regulations.
Product Certifications September 2022
16 Rosemount 3408 Level Transmitter