Owner manual

Trusted
TM
Cabinets CF800
Issue 6 Sep 05 PD-CF800 14
The instructions detailed below are applicable to whichever method of securing the cabinet in position
is used.
Install the cabinet as follows:
1. Position the cabinet in the required location using an overhead crane, forklift or rollers as
a
ppropriate.
2. Open the cabinet door and remove the split floor plate (Item 6 shown in Figure 2) to gain
access to the lower surface of the plinth.
3. Bolt the cabinet in position through the 8-off holes in the lower surface of the plinth using M12
bolts of a suitable length. Alternatively, weld the lower surface of the plinth to the floor if a
metal surface.
4. Refit the split floor plate removed in 2. then close the cabinet door.
The cabinet may be used in applications where the fitting of anti-vibration strips is necessary. Anti-
vibration Kits AV are supplied and fitted between the plinth and the floor as shown in Figure 7 below.
Figure 7 Anti-vibration Mounting