Owner manual

Publication 193-UM006A-EN-P – October 2005
DeviceNet Information B-13
The following commons services are implemented for the Parameter Object:
Parameter Group Object — CLASS CODE 0x0010
The following class attributes are supported for the Parameter Object:
The following parameter group objects are supported:
Instance 1 = Monitor Parameters
Instance 2 = Reset/Lock Parameters
Instance 3 = Advanced Setup Parameters
Instance 4 = DeviceNet Setup Parameters
Instance 5 = I/O Parameters
The following instance attributes are supported for all parameter group
instances:
Table B.31 Parameter Object Common Services
Service
Code
Implemented for:
Service Name
Class Instance
0x0E Yes Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
Table B.32 Parameter Group Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 1
2 Get Max Instance UINT 5
8 Get Native Language USINT 1= English
Table B.33 Parameter Group Object Instance Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Group Name String SHORT_STRING
2 Get Number of Members UINT
3 Get 1st Parameter UINT
4 Get 2nd parameter UINT
n Get Nth Parameter UINT