Owner manual
Publication 193-UM006A-EN-P – October 2005
4-8 Device Parameters
Jam Trip Level Parameter No. 20
This parameter sets the jam trip level. Access Rule Get/Set
Data Type UINT
Group Advanced Setup
Units % FLA
Min. Value 150
Max. Value 600
Default Value 250
Jam Warn Level Parameter No. 21
This parameter sets the jam warning level. Access Rule Get/Set
Data Type UINT
Group Advanced Setup
Units % FLA
Min. Value 100
Max. Value 600
Default Value 150
UL Inhibit Time Parameter No. 22
This parameter defines the amount of time for
which underload detection is inhibited during a
motor starting sequence.
Access Rule Get/Set
Data Type USINT
Group Advanced Setup
Units Seconds
Min. Value 0
Max. Value 250
Default Value 10
UL Warn Level Parameter No. 23
This parameter sets the underload warning
level.
Access Rule Get/Set
Data Type USINT
Group Advanced Setup
Units % FLA
Min. Value 30
Max. Value 100
Default Value 70