22 Compact High-density Analog Current Input Module
Publication 1769-IN085A-EN-P - August 2008
Bit Definitions for Channel Configuration Words
Define To Choose Make these bit settings
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Input Filter
Selection
60 Hz
0000
50 Hz
0001
16 Hz
0010
315 Hz
0011
1365 Hz
0100
Enable
Interrupt
(1)
(1) Alarm interrupts are not supported by all bus masters. Check your controller’s user manual to determine if expansion I/O
interrupts are supported.
Enable 1
Disable 0
Process
Alarm
Latch
Enable
1
Disable 0
Enable
Process
Alarms
Enable
1
Disable 0
Enable
Channel
Enable 1
Disable 0
Bit Definitions for Input Range and Input Data Configuration
Define To Choose Make these bit settings
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Input
Range
Select
4…20 mA
0000
0…20 mA
0001
Input
Data
Format
Select
Proportional
Counts
000
Engineering
Units
001
Scaled for PID 010
Percent
Range
011