Installation Instructions MicroLogix 1762-IF2OF2 Analog Input/Output Module Catalog Number 1762-IF2OF2 Topic Page Important User Information 2 North American Hazardous Location Approval 4 Additional Resources 5 Overview 6 Module Description 7 Mount the Module 8 Field Wiring Connections 11 Wiring 13 Sensor/Transmitter Types 15 I/O Memory Mapping 17 Input Data File 17 Output Data File 18 Configuration Data File 19 Specifications 21
MicroLogix 1762-IF2OF2 Analog Input/Output Module Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.
MicroLogix 1762-IF2OF2 Analog Input/Output Module 3 Environment and Enclosure ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
MicroLogix 1762-IF2OF2 Analog Input/Output Module North American Hazardous Location Approval The following modules are North American Hazardous Location approved: 1762-IF2OF2 The following information applies when operating this equipment in hazardous locations: Informations sur l’utilisation de cet équipement en environnements dangereux: Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only.
MicroLogix 1762-IF2OF2 Analog Input/Output Module 5 Additional Resources Resource Description MicroLogix 1100 Programmable Controllers User Manual, publication 1763-UM001. A more detailed description of how to install and use your MicroLogix 1100 programmable controller and expansion I/O system. MicroLogix 1200 Programmable Controllers User Manual, publication 1762-UM001. A more detailed description of how to install and use your MicroLogix 1200 programmable controller and expansion I/O system.
MicroLogix 1762-IF2OF2 Analog Input/Output Module Overview The 1762 input module is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments (Pollution degree 2(1)) and to circuits not exceeding Over Voltage Category II(2) (IEC 60664-1)(3). Install your module using these installation instructions.
MicroLogix 1762-IF2OF2 Analog Input/Output Module 7 Module Description 5 6 1a 1a 10 7 3 2 3 8 4 4 1b Front view Left side view 45156 9 45157 This equipment is sensitive to electrostatic discharge (ESD). Follow ESD prevention guidelines when handling this equipment.
MicroLogix 1762-IF2OF2 Analog Input/Output Module Mount the Module General Considerations Most applications require installation in an industrial enclosure to reduce the effects of electrical interference and environmental exposure. Locate your controller as far as possible from power lines, load lines, and other sources of electrical noise such as hard-contact switches, relays, and AC motor drives.
MicroLogix 1762-IF2OF2 Analog Input/Output Module 9 Module Spacing Maintain spacing from objects such as enclosure walls, wireways and adjacent equipment. Allow 50.8 mm (2 in.) of space on all sides for adequate ventilation, as shown: 1762 I/O 1762 I/O Side MicroLogix 1100/1200/1400 1762 I/O Top Side Bottom 44913 DIN Rail Mounting The module can be mounted using the following DIN rails: 35 x 7.5 mm (EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
MicroLogix 1762-IF2OF2 Analog Input/Output Module Panel Mounting Use the dimensional template shown below to mount the module. The preferred mounting method is to use two M4 (#8) panhead screws per module. M3.5 (#6) panhead screws may also be used, but a washer may be needed to ensure a good mechanical contact. Mounting screws are required on every module. For more than two I/O modules: measure (number of modules - 1) x 40 mm (1.59 in.) 95 (3.74) 40.4 (1.
MicroLogix 1762-IF2OF2 Analog Input/Output Module 11 Field Wiring Connections Grounding the Module In solid-state control systems, grounding and wire routing helps limit the effects of noise due to electromagnetic interference (EMI). Run the ground connection from the ground screw of the controller to the ground bus prior to connecting any devices. Use AWG #14 wire. For AC-powered controllers, this connection must be made for safety purposes.
MicroLogix 1762-IF2OF2 Analog Input/Output Module Input Type Selection Select the input type, current or voltage, using the switch located on the module’s circuit board and the input type/range selection bits in the Configuration Data File (see Configuration Data File on page 19). You can access the switch through the ventilation slots on the top of the module. Switch 1 controls channel 0; switch 2 controls channel 1. The factory default setting for both switch 1 and switch 2 is Current.
MicroLogix 1762-IF2OF2 Analog Input/Output Module 13 Wiring System Wiring Guidelines Consider the following when wiring your system: • The analog common (COM) is not connected to earth ground inside the module. All terminals are electrically isolated from the system. • Channels are not isolated from each other. • Use Belden 8761, or equivalent, shielded wire. • Under normal conditions, the drain wire (shield) should be connected to the metal mounting panel (earth ground).
MicroLogix 1762-IF2OF2 Analog Input/Output Module Differential Sensor Transmitter Types IN 0 (+) Analog Sensor IN 0 (-) IN 1 (+) IN 1 (-) Analog Load I out 0 I out 1 V out 0 V out 1 COM COM TIP Grounding the cable shield at the module end only usually provides sufficient noise immunity. However, for best cable shield performance, earth ground the shield at both ends, using a 0.01µF capacitor at one end to block AC power ground currents, if necessary.
MicroLogix 1762-IF2OF2 Analog Input/Output Module 15 Sensor/Transmitter Types 2-Wire Transmitter Power + Supply(1 Transmitter + Module - IN + - IN COM 3-Wire Transmitter Power + Supply(1) Transmitter Supply Module Signal IN + - IN COM 4-Wire Transmitter Power + Supply(1) - Transmitter Supply + - Signal Module + - IN + IN COM (1) All power supplies rated N.E.C. Class 2. Labeling the Terminals A write-on label is provided with the module.
MicroLogix 1762-IF2OF2 Analog Input/Output Module Wiring the Finger-Safe Terminal Block ATTENTION Be careful when stripping wires. Wire fragments that fall into a module could cause damage when power is applied. Once wiring is complete, ensure the module is free of all metal fragments. When wiring the terminal block, keep the finger-safe cover in place. 1. Route the wire under the terminal pressure plate. You can use the stripped end of the wire or a spade lug. The terminals will accept a 6.35 mm (0.
MicroLogix 1762-IF2OF2 Analog Input/Output Module 17 I/O Memory Mapping 1762 Expansion I/O Addressing The addressing scheme for 1762 Expansion I/O is shown below. Data file (0 or 1) Data File # 0 = Output Slot number(1) Data File # 1 = Input Word X1:x.0/0 Bit (0...15) Bit delimiter File Type Input (I) or Output (O) (1) Word delimiter Slot delimiter I/O located on the controller (embedded I/O) is slot 0. I/O added to the controller (expansion I/O) begins with slot 1.
MicroLogix 1762-IF2OF2 Analog Input/Output Module Word Scaled-for-PID Format Bit Position 15 14 13 1 0 0 0 0 Channel 0 Data 0…16,380 0 0 1 0 0 Channel 1 Data 0…16,380 0 0 2 reserved 3 reserved 4 reserved SI 1 SI 0 5 UI 0 OI 0 UI 1 12 OI 1 11 10 9 8 reserved 7 U0 0 6 O0 0 5 4 3 2 SO 1 SO 0 reserved U0 1 O0 1 reserved The bits are defined as follows: • SIx = General status bits for input channels 0 and 1.
MicroLogix 1762-IF2OF2 Analog Input/Output Module 19 Configuration Data File The configuration of the format for analog inputs and outputs is made at going to run (GTR). Changes made to the configuration file while in run mode have no effect. The configuration table for analog inputs and outputs is shown in the table below.
MicroLogix 1762-IF2OF2 Analog Input/Output Module Type/Range Select (Bits 11…8) These bits indicate the type and range as in the following table. Other combinations of these bits are not supported and result in an error. Bit Settings Data Format 11 10 9 8 0 0 1 0 0 0 1 1 other Voltage Mode 0…10V DC Current Mode 4…20 mA Not Supported Configuration via RSLogix 500 This module can be configured using RSLogix 500 programming software, as shown below.
MicroLogix 1762-IF2OF2 Analog Input/Output Module 21 Specifications General Specifications Attribute Value Dimensions, HxWxD 90 x 40.4 x 87 mm (3.54 x 1.59 x 3.43 in.) Height including mounting tabs is 110 mm (4.33 in) Approximate Shipping Weight (with carton) 240g (0.53 lbs.) Bus Current Draw (max.) 40 mA @ 5V DC 105 mA @ 24V DC Analog Normal Operating Range Voltage: 0…10V DC Current: 4…20 mA Full Scale(1) Analog Ranges Voltage: 0…10.
MicroLogix 1762-IF2OF2 Analog Input/Output Module Input Specifications Attribute Value Number of Inputs 2 differential (unipolar) A/D Converter Type Successive approximation Common Mode Voltage ±27 V Range(1) Common Mode Rejection(2) > 55 dB @ 50 and 60 Hz Non-linearity (in percent full scale) ±0.12% Typical Overall Accuracy(3) ±0.
MicroLogix 1762-IF2OF2 Analog Input/Output Module 23 Output Specifications Attribute Value Number of Outputs 2 single-ended (unipolar) D/A Converter Type Resistor string Resistive Load on Current Output 0…500 Ω (includes wire resistance) Load Range on Voltage Output > 1KΩ Reactive Load, Current Output < 0.1 mH Reactive Load, Voltage Output < 1 μF Typical Overall Accuracy ± 1.17% full scale @ -20…65 °C (-4 °F…149 °F) ±0.
MicroLogix 1762-IF2OF2 Analog Input/Output Module Environmental Specifications Attribute Value Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20... 65 °C (-4...
MicroLogix 1762-IF2OF2 Analog Input/Output Module 25 Certifications (when product is marked)(1) Attribute Value c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab.
MicroLogix 1762-IF2OF2 Analog Input/Output Module Notes: Publication 1762-IN005C-EN-P - July 2013
MicroLogix 1762-IF2OF2 Analog Input/Output Module 27 Notes: Publication 1762-IN005C-EN-P - July 2013
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.