Instructions / Assembly

POWER INLET BOX
CAT. NO. PB30
30 Amps., 120/240 VAC
INSTALLATION INSTRUCTIONS
IMPORTANT: Installation of this power inlet box and related wiring must be done by a qualified electrician in
compliance with all applicable electrical codes.
INSTALLING A REMOTELY LOCATED POWER INLET BOX FOR SUPPLYING POWER TO THE
POWER INLET OF A TRANSFER SWITCH OR PANEL
Installing the Power Inlet Box
Mount the power inlet box on the outside of the building in a convenient location, using the three holes provided in the
back of the cabinet. Using copper wire only and approved wiring methods, run the wiring through one of the
knockouts in the cabinet to a junction box located near the transfer switch. If using conduit, pull at least three color-
coded wires (AWG #10 minimum, AWG #8 maximum) -- use white for neutral, and two other distinguishing colors
(typically black and red) for the 240V line. If not using conduit or if otherwise required, include a green wire as a
separate ground wire.
Strip the wire insulation 5/8" and connect the wires in the power inlet box as follows making sure there is no wire
insulation in any terminal and the inlet terminal screws are tightened to 20 inch-pounds torque:
240 Volt line wires to the brass terminals marked "X" and "Y".
White wire to the nickel-plated neutral terminal marked "W".
Green power inlet wire to green ground screw terminal on inside of cabinet.
If required, green wire to green ground screw terminal on inside of cabinet.
Installing a junction box and cord connector
The cord assembly from the junction box to the transfer switch power inlet is to be made of four-conductor cord
suitable for a 30 Amp. load (AWG #10 minimum). The insulation on each of the wires is colored to identify with the
standardized coding in plugs and receptacles. Wire colors are usually white, green, black, and red. One end of the cord
will be connected to the wires in the junction box, and the opposite end will be connected to a NEMA Type L14-30C
connector which will mate with the power inlet on the face of the transfer switch. Remove one junction box knockout
and insert a cord grip and the cord.
Connect the wires in the junction box as follows:
Red and black cord wires to 240V line wires from the power inlet box.
White cord wire to the white neutral wire from the power inlet box.
Green cord wire to junction box ground screw.
Green wire from power inlet box, if required, to junction box ground screw.
Following the wiring device manufacturer's instructions, wire the L14-30C connector as follows:
Red and black wires to the brass terminals marked "X" and "Y".
White wire to the nickel-plated neutral terminal marked "W".
Green wire to the green ground terminal marked "G".
A diagram of the above arrangement is shown below. It is not necessary to detach the connector from the transfer
switch when generator is not in use, and for convenience may be left in place at all times.