Installation Guide
Table Of Contents
- Title
- Contents
- Introduction
- System Description
- Pre-Installation
- Receipt of Equipment
- Site Planning
- Main Rack and Supporting Hardware
- Remote ACUs
- RFUs
- RadioBlades
- RAPs
- URU
- Interconnecting Cabling
- Main Rack Configuration
- RF Planning
- Site Survey
- Alarm Configuration
- Tools Required
- Installation
- Equipment Commissioning
- iDEN Interface
- Power Plant
- RadioFrame System
- Coverage Validation
- Site Acceptance Guidelines
- RadioFrame System Functionality Test
- RadioFrame System iDEN Functionality Test
- Interconnect & Dispatch Setup & Voice Quality
- Packet Data Service Connection and Latency
- Short Message Service
- Handover and Cell Reselection
- Interconnect Connection Stability and SQE Performance
- Dispatch Connection Stability
- Idle SQE Testing and Validation
- System Self-Recovery Test
- Packet Data Stability and Throughput
- Validation of ‘Unable to Key BR’ Alarm
- Rectifier & AC Power Alarms
- iSC-3 Functionality Test
- RadioFrame System iDEN Functionality Test
- Connecting the RFS to the Customer LAN
- Operations and Maintenance
- Appendixes
Method of Procedure
Pre-Installation
44 RFN_3.1 Beta
3.5.4 Weight
• 12 lbs (fully loaded with 7 RadioBlades/RAPs)
3.5.5 Power
• Negative 36-56 Volts DC, 0.8A
3.5.6 Grounding
• No additional grounding required
3.5.7 Environment
• Operating Ambient Temperature: 0
o
C to +40
o
C (+32
o
F to +104
o
F)
• Altitude: -200 to +8000 feet above mean sea level; above 8000', reduce
maximum operating ambient temperature by 2
o
C per 1000' to a maximum of
13000'
• Storage Temperature: -40
o
C to +70
o
C (-40
o
F to +158
o
F)
• Relative Humidity: 10-90% non condensing
• Shock: 40 g’s
• Vibration: Level 3 earthquake
• Keep product free from dust, wind, salt, liquids
3.5.8 Heat Load
• 85 BTUs
3.5.9 RF Exposure
To comply with FCC RF exposure requirements, iDEN antennas must be
installed to provide at least 9 inches (20 cm) separation from all persons, with
antenna gain not exceeding zero (0) dBi.
3.5.10 Cable Support
• CAT 5 wiring to ACU