Installation Instructions

1. Check Contents. Each product package includes a fitting and a
number of stiffeners to be used on each end of pipe being connected
(i.e. 2 stiffeners for a Coupler or Elbow, 3 for a Tee).
2. Cut the pipe square. There is no need to chamfer the pipe end.
Ensure any burrs on the pipe are removed and the pipe is clean.
3. Insert stiffeners. Insert the supplied stiffeners into each end of the
pipe being connected
4. Push stiffener into pipe. Push the stiffener all the way into the pipe
until the ridge is plush with the pipe end. This can be done by hand, or
gently tapped in with a mallet if required.
5. Ensure 3 threads are showing on the fitting body. The fitting is
supplied in a ready-to-use position. You do not need to disassemble
the fitting prior to use. Always ensure 3 threads are exposed on the
central body of the fitting prior to use.
6. Mark fitting depth. To ensure correct insertion depth and achieve a
successful sealing performance, witness mark the pipe against the
flange on the central body of the fitting. Line up the pipe against the
fitting and use the flange on the central body as the guide point to
witness mark against.
7. Insert the pipe into the fitting. Gently slide the pipe into the fitting so
the end of the nut reaches the witness mark on the pipe. No force is
required to do this. Do not insert beyond this point.
8. Tighten the fitting. Tighten the nut until the nut touches the flange
on the central body of the fitting. Do not tighten further once the nut
touches the flange as overtightening can damage the fitting. It is
recommended a wrench is used to tighten the nut.
9. Fitting is installed. The fitting is now full installed and ready for use.
Note nut position relative to the flange on the central body.
Check for system leaks prior to backfilling.
WARNING! Improper installation or operation of the system may result in fire, explosion, or asphyxiation.
Only the components provided or specified by Pro-Flex LLC for use with Pro-Poly Underground® or as part
of the fuel gas system are to be used in the installation. Use of components from other flexible gas piping
systems other than those specified as part of the Pro-Poly Underground® systems is prohibited and may
result in poor system performance and serious bodily injury or property damage.
While every effort has been made to prepare this document in accordance with all regional model codes in effect at its
printing, Pro-Flex LLC cannot guarantee that the local administrative authority will accept the most recent version of these
codes. It is the ultimate responsibility of the qualified installer to determine suitability and acceptance of any building
component, including gas piping. Pro-Flex LLC, manufacturers of Pro-Poly Underground® assumes no responsibility for labor
or material for installations made without prior determination of local code authority acceptance.