User's Manual

Cod.Doc.2550041-REV02.doc
Pagina 46
A8 Generator maximum voltage 0000 / 0001 0001 = yes
A8.01 Stop without cooling 0000 / 0001 0000 = no
A8.02 Stop with cooling 0000 / 0001 0001 = yes
A8.03 Siren relay 0000 / 0001 0001 = yes
A8.04 Alarm relay (if enabled) 0000 / 0001 0001 = yes
A8.05 Not used 0000 / 0001 0000 = no
A9 Fuel 0000 / 0001 0001 = yes
A9.01 Stop without cooling 0000 / 0001 0000 = no
A9.02 Stop with cooling 0000 / 0001 0000 = no
A9.03 Siren relay 0000 / 0001 0001 = yes
A9.04 Alarm relay (if enabled) 0000 / 0001 0001 = yes
A9.05 Not used 0000 / 0001 0000 = no
A10 Maximum current 0000 / 0001 0001 = yes
A10.01 Stop without cooling 0000 / 0001 0000 = no
A10.02 Stop with cooling 0000 / 0001 0001 = yes
A10.03 Siren relay 0000 / 0001 0001 = yes
A10.04 Alarm relay (if enabled) 0000 / 0001 0001 = yes
A10.05 Not used 0000 / 0001 0000 = no
A11 Battery minimum voltage 0000 / 0001 0001 = yes
A11.01 Stop without cooling 0000 / 0001 0000 = no
A11.02 Stop with cooling 0000 / 0001 0000 = no
A11.03 Siren relay 0000 / 0001 0001 = yes
A11.04 Alarm relay (if enabled) 0000 / 0001 0001 = yes
A11.05 Not used 0000 / 0001 0000 = no
A12 Battery maximum voltage 0000 / 0001 0001 = yes
A12.01 Stop without cooling 0000 / 0001 0000 = no
A12.02 Stop with cooling 0000 / 0001 0001 = yes
A12.03 Siren relay 0000 / 0001 0001 = yes
A12.04 Alarm relay (if enabled) 0000 / 0001 0001 = yes
A12.05 Not used 0000 / 0001 0000 = no
A13 Starting failure 0000 / 0001 0001 = yes
A13.01 Stop without cooling (not influential, always as set to “no”) 0000 / 0001 0000 = no
A13.02 Stop with cooling (not influential, always as set to “no”) 0000 / 0001 0000 = no
A13.03 Siren relay 0000 / 0001 0001 = yes
A13.04 Alarm relay (if enabled) 0000 / 0001 0001 = yes
A13.05 Not used 0000 / 0001 0000 = no
E1 Remote stop 0000 / 0001 0001 = yes
E1.01 Stop without cooling (not influential, always as set to “yes”) 0000 / 0001 0001 = yes
E1.02 Stop with cooling (not influential, always as set to “no”) 0000 / 0001 0000 = no
E1.03 Siren relay 0000 / 0001 0001 = yes
E1.04 Alarm relay (if enabled) 0000 / 0001 0001 = yes
E1.05 Not used 0000 / 0001 0000 = no
E2 Emergency stop (not influential, always as set to “yes”) 0000 / 0001 0001 = yes
E2.01 Stop without cooling (not influential, always as set to “yes”) 0000 / 0001 0001 = yes
E2.02 Stop with cooling (not influential, always as set to “no”) 0000 / 0001 0000 = no
E2.03 Siren relay 0000 / 0001 0001 = yes
E2.04 Alarm relay (if enabled) 0000 / 0001 0001 = yes
E2.05 Not used 0000 / 0001 0000 = no