PTFD-10-E1RR Operators Manual Power Technology Southeast, Inc.
FORWARD You are now the proud owner of a Power Technology Generator powered by a Kubota engine. This engine is a product of Kubota’s quality engineering and manufacturing. The engine is made with fine materials and manufactured under the strictest quality control standards and will assure you long satisfactory service. To obtain the best use of your engine, please read this manual carefully.
Limited Warranty on Power Tech Generators Power Technology Southeast, Inc. warrants to you, the original purchaser, that each product of our manufacture is free from defects in materials, and workmanship. That each generator will deliver its rated output as indicated on The Power Technology Nameplate, if properly installed, serviced, and operated under normal conditions in accordance with Power Technology’s instructions.
TABLE of CONTENTS SECTION 1: “SAFETY” SAFE OPERATION SECTION 2: 1-4 “ENGINE” PRE-OPERATION CHECK OPERATING THE ENGINE ENGINE SPECIFICATIONS ENGINE MAINTENANCE SERVICE SCHEDULE ENGINE OIL MAINTENANCE ENGINE COOLANT MAINTENANCE OPERATING HOURS AND SERVICE LOG ENGINE TROUBLESHOOTING GUIDES SECTION 3: “GENERATOR END” PRINCIPLES OF OPERATION 8-10-12 KW EXCITER TYPE GENERATOR ASSEMBLY GENERATOR END TROUBLESHOOTING GUIDES WIRING SCHEMATICS SECTION 4: 1-2 3 4-6 7-10 “INSTALLATION” SAFETY PRECAUTIONS GE
SECTION 1 “SAFETY” SAFE OPERATION 1-4 Observe Safety Instructions Wear Safety Clothing Check Before Operating the Engine Keep Area Around the Engine Clean Safe Handling of Fuel and Lubricants Exhaust Gases and Fire Prevention Escaping Fluids Cautions Against Burns and Battery Explosion Keep Hands and Body Away From Rotating Parts Anti-Freeze and Disposal of Fluids Conducting Safety Checks and Maintenance This symbol, the industry’s “Safety Alert Symbol”, is used throughout this manual and on labels attac
SAFE OPERATION Cautious operation is your best insurance against an accident. Read and understand this section carefully before operating the engine. All operators, no matter how knowledgeable they may be, should read this and other related manuals before operating the engine or any equipment attached to it. It is the owner’s responsibility to instruct all operators in safe operation. Be sure to observe the following for safe operation.
KEEP AREA AROUND THE ENGINE CLEAN • Be sure to stop the engine before cleaning. • Keep the engine clean and free of accumulated dirt, grease and trash. • DO NOT stop the engine without idling; Temperatures around the engine rises suddenly. Keep the engine idling for about 5 minutes before stopping. SAFE HANDLING OF FUEL AND LUBRICANTS • Always stop the engine before refueling or lubricating. • DO NOT smoke or allow flames or sparks in your working area. Fuel is extremely flammable and explosive.
ESCAPING FLUIDS • Relieve all pressure in the air, oil and cooling systems before any lines, fittings or related items are removed or disconnected. • Be alert for possible pressure release when disconnecting any device from a system that is pressurized. DO NOT check for pressure leaks with your hands. High-pressure oil or fuel can cause personal injury. • Escaping hydraulic fluid under pressure has sufficient force to penetrate skin causing serious personal injury.
ANTI-FREEZE AND DISPOSAL OF FLUIDS • Anti-freeze contains toxic chemicals. Wear rubber gloves when handling anti-freeze. In case of contact with skin, wash immediately to avoid personal injury. • DO NOT mix different types of Anti-freeze. The mixture can produce a chemical reaction resulting in the formation of harmful substances. Only use anti-freeze that is recommended and approved by Caterpillar. • Be mindful of the environment.
SECTION 2 “ENGINE” PRE-OPERATION CHECK 1 Engine Break-in Period Daily Check OPERATING THE ENGINE 2 Engine Starting Controls Starting the Engine Check Engine After Starting Stopping the Engine ENGINE SPECIFICATIONS 3 Kubota Models D1105-EBG1 and V1505-EBG1 Service Parts ENGINE MAINTENANCE SERVICE SCHEDULE 4 ENGINE OIL MAINTENANCE 5 Checking Engine Oil Level Lubricating Oil Specifications Engine Refill Capacities Lubricating Oil Viscosity Recommendations ENGINE COOLANT MAINTENANCE 6 Coolant Re
PRE-OPERATION CHECK ENGINE BREAK-IN PERIOD During the engine break-in period, observe the following recommendations: 1. Change the engine oil and oil filter cartridge after the first 50 hours of operation. (See “ENGINE OIL” in ENGINE MAINTENANCE SERVICE SCHEDULE). 2. In ambient temperature above 32°F (0°C) approximately 3-5 minutes without a load is sufficient for engine warm up. Allow additional warm up time when temperatures are below 32°F (0°C) before placing an operating load on the engine.
OPERATING THE ENGINE ENGINE STARTING CONTROLS 1) 2) 3) 4) 5) Generator Main Switch must be in the ON position. Hold Start/Stop Switch for 1 second and release. Glow Plugs will preheat for 8 seconds. LED flashes slowly. Preheating will cease during engine cranking cycle. LED continues flashing. Engine begins an 8 seconds crank cycle, After 4 seconds of cranking the PT-ECU-63 will check for an AC signal from the generator.
ENGINE SPECIFICATIONS MODEL Kubota D1105-EBG1 Kubota V1505-EBG1 Continuous Output 13.6HP @ 1800 rpm 17.9HP @ 1800 rpm Cubic Capacity 68.53 in³ (1.123.L) 91.41in³ (1.498L) Bore and Stroke 3.07” x 3.09” (78.0 x 78.4mm) 3.07” x 3.09” (78.0 x 78.4mm) 3 In-Line 4 In-Line Firing Order 1-2-3 1-3-4-2 Compression Ratio 22:1 22:1 Engine Oil Capacity 5.38qts. (5.1L) 6.34 qts. (6.0L) Coolant Capacity 3.27qts. (3.1L) 4.22qts. (4.0L) Fuel and Type Diesel No. 2-D 4 Cycle Diesel No.
Engine Maintenance Service Schedule Maintenance Service Item *See Note Engine Oil Level Deterioration & Leakage Engine Oil Change Min.
ENGINE OIL MAINTENANCE CHECKING ENGINE OIL LEVEL KUBOTA ENGINE REFILL CAPACITIES Crankcase Oil Sump and Filter D1105-EBG1 5.38Qts. (5.1L) V1505-EBG1 6.34Qts. (6.0L) LUBRICATING OIL VISCOSITY RECOMMENDATIONS ( Y ) “ADD” mark. ( X ) “FULL” mark. 1. Maintain the engine oil level between “ADD” mark and “FULL” mark on oil level gauge. Do not fill crankcase above “FULL” mark. 2. Remove the oil filler cap and add oil, if necessary. Clean the oil filler cap. Install the oil filler cap.
ENGINE COOLANT MAINTENANCE COOLANT RECOMMENDATIONS COOLANT SERVICE LIFE For optimum performance, Power Technology recommends a 1:1 mixture of water / glycol. Coolant Type NOTE: Use a mixture that will provide protection against the lowest ambient temperature. NOTE: 100 percent pure glycol will freeze at a temperature of –23°C (-9°F). Most conventional heavy-duty coolant / antifreezes use Ethylene Glycol. Propylene Glycol may also be used in a 1:1 mixture with water.
OPERATING HOURS and SERVICE LOG THIS SERVICE LOG IS PROVIDED TO HELP YOU KEEP AN ACCUMULATIVE RECORD OF OPERATION HOURS ON YOUR GENERATOR SET AND THE DATES REQUIRED SERVICES WERE PERFORMED. ENTER TIME TO THE NEAREST HOUR. OPERATING HOURS DATE HRs.
ENGINE STARTS BUT WON’T RUN Engine Runs OK Unplug Remote Start-Stop from Control Box Problem with Remote Connection.
ENGINE RUNS ROUGH or SLOW NO Visible Exhaust Smoke Excessive Exhaust Smoke BLUE Insufficient Fuel to Engine GRAY/WHITE Excessive Oil Level BLACK Check Fuel Level Replace Fuel Filter Dirty Air Filter Engine Overheated Air IN Fuel System Check Fuel PUMP Engine Over Loaded Clogged Muffler Over Fueling Injector Check Safety Shutdowns And Fuel Solenoid HIGH ALTITUDE Engine Cold Incomplete Combustion Glow Plug Not Activating Check With 12 volt DC Test Light 9 Over-fueling Injector
ENGINE WILL NOT START Engine Does NOT Crank Engine Cranks Main Switch NO Exhaust Smoke Smoke From Exhaust Check Fuel Solenoid YES Check Fuel Pump Starter Relay Check Glow Plug Relay Starter Motor NO Defective Solenoid Air IN Fuel System Battery Dead Start Switch Check Glow Plugs Check Fuel Supply NO Power While Cranking Turn Switch “ON” Check Spark Arrestor Muffler for Clogging No Power From Starter Terminal 10 Engine Cranks SLOW Oil Viscosity TOO HEAVY Check Terminal Ends LOW Batte
SECTION 3 “GENERATOR END” GENERATOR ASSEMBLY INFORMATION 1-2 Brush Type Exciter Type Electronic Voltage Regulation Voltage Connection Field Coil Voltage Source (Exciter Type Only) Rotating Field Assembly (Rotor) Core Assembly Field Coil Balance Bearing Stator Assembly EXCITER TYPE “C” GENERATOR ASSEMBLY BRUSH TYPE “C” GENERATOR ASSEMBLY __________ GENERATOR END TROUBLESHOOTING GUIDES 3 4 5-7 Zero or Low Voltage Voltage Test 12-Volt Battery Test Overload Condition WIRING SCHEMATICS 120 Volt Connecti
GENERATOR ASSEMBLY INFORMATION BRUSH and EXCITER TYPE GENERATOR BRUSH TYPE Brush Type generators use a set of carbon or graphite brushes that are set into a spring loaded brush holder, which house and support the brushes. This brush holder is mounted in such a way as to allow the brushes to maintain a sliding electrical contact between the stationary and rotating components of the generator.
FIELD COIL VOLTAGE SOURCE (EXCITER TYPE ONLY) Field coil DC voltage is obtained by rectifying the voltage from the phase to neutral line of the generator output, or either appropriate terminal to provide the needed voltage reference. The rectifier bridge is an internal part of the static regulator. The static regulator senses a change in the generator output and automatically regulates current flow in the exciter field coil circuit to increase or decrease the exciter field strength.
3 DESCRIPTION PART NUMBER 8KW 10KW 12KW 1. BEARING PLATE 02BR-CR 02BR-CR 02BR-CR 2. END BELL 02H7810 02H10KW-CR 02H10KW-CR 3.EXCITER STATOR 02STA8EXC 02STA10EXCR 02STA12EXCR 4. MAIN STATOR 02STAMNCD8 02STACI7210 02STAMN12 5. BELL HOUSING ** 02BHTPU7 02BHTPU7 02BHTPU7 6. ROTOR BEARING 02BRG6206 02BRG6206 02BRG6206 7. DIODE PLATE 02PLD8CD 02PLD8CD 02PLD8CD 8. EXCITER ROTOR 02RTR8EXC 02RTR10EXCR 02RTR12EXCR 9. MAIN ROTOR 02RTRMN8EXC 02RTR10E 02RTR12E 10. END BELL ASSEMBLY 02EB8 02EB10 02EB12 11.
4 DESCRIPTION 1. COVER SCREEN 2. BEARING PLATE 3. STATOR ASSEMBLY ** 4. ROTOR BEARING 5. BRUSH SET 6. ROTOR ASSEMBLY ** NOTE: Item #3 MAIN STATOR ASSEMBLY is a one-piece unit. The Stator cannot be separated from the Generator’s outer housing.
ZERO OR LOW VOLTAGE Check Main Breaker is “ON” Check Gen Fuse BAD OK ON OFF Main Coil Output to Breaker Replace Fuse Turn “ON” Breaker OK BAD Wiring To Panel Defective Breaker Check Ohm’s on Exciter Leads OK BAD Replace Exciter OK Replace Voltage Regulator 5 12 V Battery Test
VOLTAGE TEST Zero or Low Voltage Check Main Breaker On GenSet Overload High Voltage Output Voltage OK Check AMP Draw From equipment Replace AVR Check Load Distribution One Voltage Line may be Higher than the other Check Gen End 12 VOLT BATTERY TEST One Coil Low Voltage Replace Stator Both Coils Low Voltage Sensing Voltage Low or None Replace Stator Check Connections Check Engine RPM 1800 Replace Stator 6 Replace AVR
OVERLOAD CONDITION Check AMP Draw Check Load Distribution Disconnect AVR Conduct 12-Volt Battery Test BAD OK Engine Problem Check Stator Coil Resistance BAD See Engine Troubleshooting Replace Stator 7 OK Replace AVR And Test
POWER TECHNOLOGY SOUTHEAST, INC. 634 STATE ROAD 44 LEESBURG, FL 34748-8103 (352) 365-2777 FAX (352) 787-5545 KW MAIN STATOR MAIN ROTOR EXCITER STATOR EXCITER ROTOR AUX. WINDING BATT. CHARGE SENSING WINDING 8 0.5 1.9 86.9 33.8 2.5 0.5 0.4 10 0.5 2.0 87.4 33.8 1.6 0.5 0.4 12 0.5 2.2 89.0 34.0 1.5 0.5 0.
POWER TECHNOLOGY SOUTHEAST, INC. 634 STATE ROAD 44 LEESBURG, FL 34748-8103 (352) 365-2777 FAX (352) 787-5545 KW MAIN STATOR MAIN ROTOR EXCITER STATOR EXCITER ROTOR AUX. WINDING BATT. CHARGE SENSING WINDING 8 0.5 1.9 86.9 33.8 2.5 0.5 0.4 10 0.5 2.0 87.4 33.8 1.6 0.5 0.4 12 0.5 2.2 89.0 34.0 1.5 0.5 0.
RESISTANCE CHART POWER TECHNOLOGY SOUTHEAST, INC. 634 STATE ROAD 44 LEESBURG, FL 34748-8103 (352) 365-2777 FAX (352) 787-5545 KW MAIN STATOR MAIN ROTOR AUX. WINDING BATT. CHARGE SENSING WINDING 8 0.257 83.1 2.64 0.159 0.
RESISTANCE CHART POWER TECHNOLOGY SOUTHEAST, INC. 634 STATE ROAD 44 LEESBURG, FL 34748-8103 (352) 365-2777 FAX (352) 787-5545 KW MAIN STATOR MAIN ROTOR AUX. WINDING BATT. CHARGE SENSING WINDING 8 0.257 83.1 2.64 0.159 0.
RESISTANCE CHART POWER TECHNOLOGY SOUTHEAST, INC. 634 STATE ROAD 44 LEESBURG, FL 34748-8103 (352) 365-2777 FAX (352) 787-5545 KW MAIN STATOR MAIN ROTOR AUX. WINDING BATT. CHARGE SENSING WINDING 8 0.257 83.1 2.64 0.159 0.
RESISTANCE CHART POWER TECHNOLOGY SOUTHEAST, INC. 634 STATE ROAD 44 LEESBURG, FL 34748-8103 (352) 365-2777 FAX (352) 787-5545 KW MAIN STATOR MAIN ROTOR AUX. WINDING BATT. CHARGE SENSING WINDING 8 0.257 83.1 2.64 0.159 0.
RESISTANCE CHART POWER TECHNOLOGY SOUTHEAST, INC. 634 STATE ROAD 44 LEESBURG, FL 34748-8103 (352) 365-2777 FAX (352) 787-5545 KW MAIN STATOR MAIN ROTOR AUX. WINDING BATT. CHARGE SENSING WINDING 10 0.093 72.5 0.892 0.082 0.029 12 0.093 72.5 0.892 0.082 0.
RESISTANCE CHART POWER TECHNOLOGY SOUTHEAST, INC. 634 STATE ROAD 44 LEESBURG, FL 34748-8103 (352) 365-2777 FAX (352) 787-5545 KW MAIN STATOR MAIN ROTOR AUX. WINDING BATT. CHARGE SENSING WINDING 10 0.093 72.5 0.892 0.082 0.029 12 0.093 72.5 0.892 0.082 0.
SECTION 4 “INSTALLATION” SAFETY PRECAUTIONS 1-2 Hot Piping Dangerous Fuels Explosive Battery Gases Electrocution Moving Parts High Voltage Explosion Hot Coolant Lethal Exhaust Gas Excessive Noise Electrical Shock Backfire Flash Fire Fire Hazard Marine Application Unit Starts Without Notice Loose Components GENERATOR INSTALLATION in RECREATIONAL VEHICLES 3-6 Introduction Marine Application General Information Specification Charts Fuel Consumption in Gallons per Hour Installation Factors Generator Compar
SAFTEY PRECAUTIONS A generator set can be potentially dangerous if not properly maintained and operated. The best Safe Guard against a dangerous situation is education, good judgment and common sense. For safe trouble free operation of your generator set some general precautions are listed below. Be sure to read, understand and follow these precautions. Please call Power Technology Southeast, Inc. with any concerns you may have with your generator set.
7) EXPLOSION: Never connect the negative (-) battery cable to the positive (+) connection terminal of the starter solenoid, or test the battery by shorting terminals together. This could ignite fuel vapors or cause the battery to explode. To disconnect the battery remove the negative battery cable first and reconnect it last. Do not modify the fuel tank or propulsion engine fuel system. Your vehicle must be equipped with a fuel pick-up arrangement as described in the Fuel System section of this manual.
GENERATOR INSTALLATION in RECREATIONAL VEHICLES INTRODUCTION Use this section as a guide when installing a generator set in a recreational vehicle, and then refer to the appropriate operation section for specific instructions. The installation of a RV generator set shall comply with current standards of ANSI / RVIA EGS-1, NFPA 1192 / ANSI A 119.2, ANSI / NFPA 70, NFPA 551 and applicable articles of the National Electrical Code. Generator set installations must also comply with state and local requirements.
SPECIFICATION CHARTS FUEL CONNECTION FUEL RECOMMENDATION BATTERY VOLTAGE BATTERY CRANKING AMPS BATTERY COLD CRANKING AMPS BATTERY GROUND ¼” NPT DIESEL FUEL No.1-D or No.2-D ASTM / D975 12 VOLTS DC 420 590 MINIMUM NEGATIVE FUEL CONSUMPTION IN GALLONS PER HOUR LOAD PERCENTAGE 25% 50% 75% 100% 8KW .21 GPH .40 GPH .60 GPH .80 GPH 10KW .26 GPH .47 GPH .74 GPH 1.0 GPH 12KW .32 GPH .49 GPH .90 GPH 1.
GENERATOR COMPARTMENT SIZE In planning the size of the generator compartment or bay allow for the minimum clearance necessary to adequately cool the generator set. The thickness of insulation and sound deadening material used to line the compartment must be taken into consideration when planning this clearance. To maintain minimum clearance it may be necessary to enlarge the compartment. The generator set must be securely fastened to avoid unwanted movement from vibration and road shock.
AIR REQUIREMENTS CONT’D 8KW 1800 13.6 N/A 160°F 185°F 230°F 230°F 929 56709 1700 268°F N/A ENGINE SPEED IN RPM OUTPUT IN HORSEPOWER ENGINE INLET WATER TEMP. THERMOSTAT RATING THERMOSTAT FULL OPEN ENGINE OUTLET WATER TEMP.MAX. HIGH TEMP. SHUTDOWN SWITCH HEAT REJECTION – BTU / MIN. HEAT REJECTION – BTU / HR. AIR FLOW – CU. FT. / MIN. ENGINE OIL TEMP. MAX. COMBUSTION AIR TEMP. * 10KW 1800 17.9 N/A 160°F 185°F 230°F 230°F 979 58770 1700 268°F N/A 12KW 1800 17.
SYSTEMS CONNECTION REMOTE RADIATOR COOLING SYSTEM Use the following data in designing and installing the generator set cooling system. To insure a safe effective installation, be sure the cooling system selected follows these parameters. Power Technology offers radiator assemblies, which meet these requirements and will adequately cool the generator. Select the radiator assembly best suited for the generator installation.
SYSTEMS CONNECTION FUEL SYSTEM The diesel fuel system for the generator set must be designed to operate independently from the vehicles main engine if both engines are to be operated at the same time. The best way to do this is to have separate fuel tanks, but this is usually impractical because of space restrictions. In most installations both engines operate from a common fuel tank with separate pick-up tubes for each engine, not a Tee fitting arrangement.
EXHAUST SYSTEM IMPORTANT SAFETY TIPS: When exhaust system components are not furnished by Power Technology as part of the Genset, the installer is responsible for meeting the following requirements. 1) Only use exhaust system components, which do not restrict exhaust flow. A restricted exhaust system will create excessive backpressure and may cause poor engine performance and possible engine damage.
12
ELECTRICAL CONNECTIONS ELECTRICAL WIRING All wiring must be applicable with local electrical codes. A qualified licensed electrician must perform all electrical wiring connections. Ground Fault (GFCI) breakers must be installed to protect all vehicle branch circuits. All switches and controls must be securely mounted to prevent damage and accidental opening or closing from vibration, road shock and vehicle motion.
MOTOR LOADS When figuring generator set capacity requirements for installation involving motor loads, do not overlook the high current demanded by the motor during start-up. The “In-Rush” of starting current may be 2 to 5 times higher than that required when the motor reaches normal operating speed. Reserve capacity must be allowed for in rush demands plus other loads, which could be on the line as the motor starts.
APPLIANCE LOADS Generator sets in recreational vehicles are often used to supply AC voltage for appliances. With the exception of a resistance-type load such as a water heater, requirements for appliances are usually low. However, such loads must not be overlooked when calculating the total wattage requirements. To avoid an overload situation, reserve capacity should also be calculated for unanticipated appliance loads.
ES52F ENGINE CONTROLLER The ES52F Engine Controller is designed to enable automatic Start/Stop capability as well as providing fault protection for the generator. The ES52F will automatically Start the generator upon command and will monitor vital engine and generator functions. In the event a failure was to occur, the ES52F will automatically Stop the engine thus preventing further problems.
TROUBLESHOOTING Trouble Possible Cause Suggested Action Unit does not operate when powered to test mode Power leads to unit are reversed. Bad ground connection from engine to controller unit. Battery is low or terminals are dirty. Crank circuitry wiring improperly connected. Bad ground connection from engine to controller. Crank relay damaged. Or on board fuse is blown. Confirm correct wiring for ground And bat, and re-attempt testing.
PT-ECU-63 ENGINE CONTROL MODULE 1) 2) 3) 4) 5) Generator Main Switch must be in the ON position. Hold Start/Stop Switch for 1 second and release. Glow Plugs will preheat for 8 seconds. LED flashes slowly. Preheating will cease during engine cranking cycle. LED continues flashing. Engine begins an 8 seconds crank cycle, After 4 seconds of cranking the PT-ECU-63 will check for an AC signal from the generator.
BLUE to 12V GENERATOR WINDING BLUE to 12V GENERATOR WINDING RED to +12V DC YELLOW to RUN RELAY BLACK to GROUND GREEN NOT USED 06REG12DC 19 06REG12DCAT 12 VOLT DC CHARGING
POWER TECHNOLOGY SOUTHEAST, INC.
OVERLOAD CONDITION Check AMP Draw Check Load 10 Engine Problem See Engine Troubleshooting Check Stator Coil Resistance Replace Stator