User Manual
PNOZ X3
Operating Manual PNOZ X3
20547-EN-08
29
Conventional thermal current
while loading several contacts
774318 774319
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 8 A 8 A
Conv. therm. current with 2 con-
tacts 8 A 8 A
Conv. therm. current with 3 con-
tacts 7 A 7 A
Times 774318 774319
Switch-on delay
With automatic start typ. 250 ms 250 ms
With automatic start max. 500 ms 500 ms
With automatic start after power
on typ. 280 ms 280 ms
With automatic start after power
on max. 550 ms 550 ms
With monitored start typ. 35 ms 35 ms
With monitored start max. 50 ms 50 ms
Delay-on de-energisation
With E-STOP typ. 15 ms 15 ms
With E-STOP max. 30 ms 30 ms
With power failure typ. 50 ms 50 ms
With power failure max. 70 ms 70 ms
Recovery time at max. switching
frequency 1/s
After E-STOP 50 ms 50 ms
After power failure 100 ms 100 ms
Waiting period with a monitored
start 300 ms 300 ms
Min. start pulse duration with a
monitored start 30 ms 30 ms
Supply interruption before de-ener-
gisation 20 ms 20 ms
Simultaneity, channel 1 and 2 max. ∞ ∞
Environmental data 774318 774319
Climatic suitability EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -20 - 55 °C -20 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during operation Not permitted Not permitted
EMC EN 12015, EN 12016, EN
60947-5-1, EN 61000-6-2, EN
61326-3-1
EN 12015, EN 12016, EN
60947-5-1, EN 61000-6-2, EN
61326-3-1