User Manual

PNOZ 16S
Operating Manual PNOZ 16S
1003518-EN-07
23
Environmental data 774074 774075 774076 774077
Ambient temperat-
ure
Temperature
range -10 - 55 °C -10 - 55 °C -10 - 55 °C -10 - 55 °C
Storage temperature
Temperature
range -40 - 85 °C -40 - 85 °C -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during
operation Not permitted Not permitted Not permitted Not permitted
EMC EN 60947-5-1, EN
61000-6-2, EN
61326-3-1
EN 60947-5-1, EN
61000-6-2, EN
61326-3-1
EN 60947-5-1, EN
61000-6-2, EN
61326-3-1
EN 60947-5-1, EN
61000-6-2, EN
61326-3-1
Vibration
In accordance
with the standard EN 60068-2-6 EN 60068-2-6 EN 60068-2-6 EN 60068-2-6
Frequency 10 - 55 Hz 10 - 55 Hz 10 - 55 Hz 10 - 55 Hz
Amplitude 0,35 mm 0,35 mm 0,35 mm 0,35 mm
Airgap creepage
In accordance
with the standard EN 60947-1 EN 60947-1 EN 60947-1 EN 60947-1
Overvoltage cat-
egory III / II III / II III / II III / II
Pollution degree 2 2 2 2
Rated insulation
voltage 250 V 250 V 250 V 250 V
Rated impulse with-
stand voltage 4 kV 4 kV 4 kV 4 kV
Protection type
Mounting area
(e.g. control cab-
inet) IP54 IP54 IP54 IP54
Housing IP40 IP40 IP40 IP40
Terminals IP20 IP20 IP20 IP20
Mechanical data 774074 774075 774076 774077
Mounting position Any Any Any Any
Mechanical life 10,000,000 cycles 10,000,000 cycles 10,000,000 cycles 10,000,000 cycles
Material
Bottom PPO UL 94 V0 PPO UL 94 V0 PPO UL 94 V0 PPO UL 94 V0
Front ABS UL 94 V0 ABS UL 94 V0 ABS UL 94 V0 ABS UL 94 V0
Top PPO UL 94 V0 PPO UL 94 V0 PPO UL 94 V0 PPO UL 94 V0
Connection type Screw terminal Screw terminal Screw terminal Screw terminal
Mounting type Fixed Fixed Fixed Fixed