User Manual

PNOZ X7
Operating Manual PNOZ X7
19692-EN-05
20
Times 774055 774056 774057
Delay-on de-energisation
With E-STOP typ. 70 ms 70 ms 70 ms
With E-STOP max. 100 ms 100 ms 100 ms
With power failure typ. 70 ms 70 ms 70 ms
With power failure max. 100 ms 100 ms 100 ms
Recovery time at max.
switching frequency 1/s
After E-STOP 120 ms 120 ms 120 ms
After power failure 120 ms 120 ms 120 ms
Supply interruption before
de-energisation 20 ms 20 ms 20 ms
Environmental data 774055 774056 774057
Climatic suitability EN 60068-2-78 EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C -10 - 55 °C -10 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during op-
eration Not permitted Not permitted Not permitted
EMC EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
Vibration
In accordance with the
standard EN 60068-2-6 EN 60068-2-6 EN 60068-2-6
Frequency 10 - 55 Hz 10 - 55 Hz 10 - 55 Hz
Amplitude 0,35 mm 0,35 mm 0,35 mm
Airgap creepage
In accordance with the
standard EN 60947-1 EN 60947-1 EN 60947-1
Overvoltage category III / II III / II III / II
Pollution degree 2 2 2
Rated insulation voltage 250 V 250 V 250 V
Rated impulse withstand
voltage 4 kV 4 kV 4 kV
Protection type
Mounting area (e.g.
control cabinet) IP54 IP54 IP54
Housing IP40 IP40 IP40
Terminals IP20 IP20 IP20
Mechanical data 774055 774056 774057
Mounting position Any Any Any