User Manual

PNOZ X7
Operating Manual PNOZ X7
19692-EN-05
10
Installation
} The unit should be installed in a control cabinet with a protection type of at least IP54.
} Use the notch on the rear of the unit to attach it to a DIN rail.
} Ensure the unit is mounted securely on a vertical DIN rail (35 mm) by using a fixing ele-
ment (e.g. retaining bracket or an end angle).
Wiring
Please note:
} Information given in the "Technical details [ 14]" must be followed.
} Calculating the max. cable length I
max
in the input circuit on PNOZ X7 24 VAC/DC:
R
lmax
R
l
/ km
I
max
=
R
lmax
= max. overall cable resistance (see Technical details [ 14])
R
l
/km = cable resistance/km
} Calculating the max. cable length I
max
in the input circuit on PNOZ X7 AC units:
C
C
C
lmax
= max. overall line capacitance (see Technical details [ 14])
C
l
/km = line capacitance/km
Stub circuit: The max. permitted cable length I
max
depends on the max. overall line ca-
pacitance C
lmax
(see Technical details [ 14]).
Alternative: Loop circuit: Capacitance is negligible; 1 phase: Max. cable length I
max
: 1
km
Stub circuit Loop circuit
Cable length
l
max
l
max
WARNING!
If the max. overall line capacitance is exceeded, the unit will no longer
switch off safely and serious injuries and death may result.
Always comply with the max. overall line capacitance.