} Use copper wiring with a temperature stability of 75 °C.
Please note the following when connecting to Ethernet POWERLINK:
} The following minimum requirements of the connection cable and connector must be
met:
Only use standard industrial Ethernet cable and connectors.
Only use double-shielded twisted pair cable and shielded RJ45 connectors (indus-
trial connectors).
100BaseTX cable in accordance with the Ethernet standard (min. Category 5)
} Measures to protect against interference:
Ensure the requirements for the industrial use of Ethernet POWERLINK are met, as
stated in the Installation Manual published by the User Group.
} External measures must be used to connect the terminal
to the functional earth,
when the mounting rail is not connected to the functional earth.
} Always connect the mounting rail to the protective earth via an earthing terminal. This
will be used to dissipate hazardous voltages in the case of a fault.
} The power supply must meet the regulations for extra low voltages with protective sep-
aration.
Connecting the supply voltage
Connect the supply voltage to the fieldbus module:
} 24 V terminal: + 24 VDC
} 0 V terminal: 0 V
} Protect the supply voltage as follows:
Circuit breaker, characteristic C - 6 A
or
Blow-out fuse, slow, 6A