Datasheet
PNOZmulti 2 products
Input and output modules
PNOZ m EF 4DI4DOR
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
718
Mechanical data
Dimensions
Height 101,4 mm
Width 22,5 mm
Depth 120,0 mm
Weight 190 g
Where standards are undated, the 2012-04 latest editions shall apply.
Safety characteristic data
Unit Operating
mode
EN ISO
13849-1: 2008
PL
EN ISO
13849-1: 2008
Category
EN 62061
SIL CL
EN 62061
PFH
D
[1/h]
EN ISO
13849-1: 2008
T
M
[year]
Logic
CPU – PL e Cat. 4 SIL CL 3 2,84E-10 20
Input
SC inputs 1-channel PL d Cat. 2 SIL CL 2 2,10E-09 20
SC inputs 2-channel PL e Cat. 4 SIL CL 3 4,27E-11 20
SC inputs 1-ch., pulsed
light barrier
PL e Cat. 4 SIL CL 3 2,10E-10 20
Output
Relay outputs 1-channel PL c Cat. 1 - 3,75E-08 20
Relay outputs 2-channel PL e Cat. 4 SIL CL 3 7,52E-12 20
Requirement on 1-channel relay outputs for Category 1 in accordance with EN 13849-1: An
additional output switches to a safe condition in the event of an error or, if that is im-
possible, signals a hazardous condition.
All the units used within a safety function must be considered when calculating the safety
characteristic data.
The PFH value depends on the switching frequency and the load on the relay output.
If the service life graphs are not accessible, the stated PFH value can be used irrespective
of the switching frequency and the load, as the PFH value already considers the relay's
B10d value as well as the failure rates of the other components.