Datasheet
PNOZmulti Mini products
Link modules
PNOZ mml1p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
572
yellow
white
orange
blue
yellow
white
orange
blue
yellow
white
orange
blue
yellow
white
orange
blue
SafetyNET p Connector RJ45 SafetyNET p Connector RJ45
SafetyNET p Cable
A B C D
A B C D
PIN 1
PIN 3
PIN 2
PIN 6
PIN 6
PIN 2
PIN 3
PIN 1
Connection cable configuration when using:
- 2 plug-in connectors "SafetyNET p Connector RJ45"
- 1 connection cable "SafetyNET p Cable"
(available as accessory, see order reference)
Connection examples
Example: Series connection of 3 base units
Reaction time t
SUM
between base unit Base 1 and Base 2:
Input delay t
ON
at I4 and I6 + data transmission time1 * t
BUS
through link module/interface +
switch-off delay t
COND
of the semiconductor output at O0
t
SUM
= t
ON
+ (n * t
BUS
) + t
COND
t
SUM
= 4 ms + (1 * 35 ms ) + 30 ms = 69 ms
Reaction time t
SUM
between base unit Base 1 and Base 3:
Input delay t
ON
at I4 und I6 + data transmission time 2 * t
BUS
through link modules/interfaces
+ switch-off delay t
COND
of the semiconductor output at O1
t
SUM
= t
ON
+ (n * t
BUS
) + t
COND
t
SUM
= 4 ms + (2 * 35 ms ) + 30 ms = 104 ms
K2
I3
I6
Base 1 Base 2 Base 3
S1
K3