Datasheet

PNOZmulti products
Fieldbus modules
PNOZ mc9p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
474
Please note the following when connecting to PROFINET:
} The following minimum requirements of the connection cable and connector must be
met:
Only use standard industrial Ethernet cable and connectors.
Only use double-shielded twisted pair cable and shielded RJ45 connectors (indus-
trial connectors).
100BaseTX cable in accordance with the Ethernet standard (min. Category 5)
} Measures to protect against interference:
Ensure the requirements for the industrial use of PROFINET are met, as stated in the
Installation Manual published by the User Group.
} Always connect the mounting rail to the protective earth via an earthing terminal. This
will be used to dissipate hazardous voltages in the case of a fault.
} The power supply must meet the regulations for extra low voltages with protective sep-
aration.
Interface assignment
RJ45 socket
8-pin
PIN Standard
8 1
1 TD+ (Transmit+)
2 TD- (Transmit-)
3 RD+ (Receive+)
4 n.c.
5 n.c.
6 RD- (Receive-)
7 n.c.
8 n.c.
n.c.: Not connected
Preparing for operation
Assign unit name
The unit name is assigned in the PNOZmulti Configurator. When selecting the PNOZ mc9p,
enter the unit name under Equipment Identifier.
} You can also assign the unit name through the IO Controller. In this case, insert a "$"
symbol in front of the unit name in the PNOZmulti Configurator, under Equipment
Identifier.