Datasheet

PNOZmulti products
Fieldbus modules
PNOZ mc7p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
454
Input and output data
The data is structured as follows:
} Input area
Inputs on PNOZmulti Configurator: i00 … i23
Input data CC-Link: RY0n, RY1n with n = 0 … F
Example: i23 -> RY17
n F E D C B A 9 8 7 6 5 4 3 2 1 0
RY0n i15 i14 i13 i12 i11 i10 i09 i08 i07 i06 i05 i04 i03 i02 i01 i00
RY1n - - - - - - - - i23 i22 i21 i20 i19 i18 i17 i16
} Output range
Outputs on PNOZmulti Configurator: o00 … o23
Output data CC-Link: RXn, RX1n with n = 0 … F
Example: o22 -> Rx16
n F E D C B A 9 8 7 6 5 4 3 2 1 0
RX 0n o15 o14 o13 o12 o11 o10 o09 o08 o07 o06 o05 o04 o03 o02 o01 o00
RX 1n - - - - - - - - o23 o22 o21 o20 o19 o18 o17 o16
The number of virtual inputs and outputs can be extended to 128 (see document "Commu-
nication Interfaces" in the section entitled "Fieldbus modules")
Detailed information on data exchange is available in the document "Communication Inter-
faces PNOZmulti 2" in the section entitled "Fieldbus modules".
Block diagram
Base unit
DA
FG/PE
DB
DG
SLD
CC-Link