Environmental data
Storage temperature
In accordance with the standard EN 60068-2-1/-2
Temperature range -25 - 70 °C
Climatic suitability
In accordance with the standard EN 60068-2-30, EN 60068-2-78
Humidity 93 % r. h. at 40 °C
Condensation during operation Not permitted
EMC EN 61131-2
Vibration
In accordance with the standard EN 60068-2-6
Frequency 10,0 - 150,0 Hz
Acceleration 1g
Shock stress
In accordance with the standard EN 60068-2-27
Acceleration 15g
Duration 11 ms
Max. operating height above sea level 2000 m
Airgap creepage
In accordance with the standard EN 61131-2
Overvoltage category III
Pollution degree 2
Rated insulation voltage 30 V
Protection type
In accordance with the standard EN 60529
Mounting area (e.g. control cabinet) IP54
Housing IP20
Terminals IP20
Potential isolation
Potential isolation between Module and system voltage
Type of potential isolation Functional insulation
Rated surge voltage 500 V
Mechanical data
Mounting position Horizontal on top hat rail
DIN rail
Top hat rail 35 x 7,5 EN 50022
Recess width 27 mm
Material
Bottom PPO UL 94 V0
Front ABS UL 94 V0
Connection type Spring-loaded terminal, screw terminal