Datasheet
PNOZmulti products
Link modules
PNOZ ml1p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
256
Mechanical data 773540 773545
Mounting position Horizontal on top hat rail Horizontal on top hat rail
DIN rail
Top hat rail 35 x 7,5 EN 50022 35 x 7,5 EN 50022
Recess width 27 mm 27 mm
Max. cable length between two link
modules
1 km 1 km
Material
Bottom PPO UL 94 V0 PPO UL 94 V0
Front ABS UL 94 V0 ABS UL 94 V0
Connection type Spring-loaded terminal, screw
terminal
Spring-loaded terminal, screw
terminal
Conductor cross section with screw
terminals
1 core flexible 0,25 - 1,50 mm², 24 - 16 AWG 0,25 - 1,50 mm², 24 - 16 AWG
2 core with the same cross sec-
tion, flexible without crimp con-
nectors or with TWIN crimp con-
nectors
0,25 - 0,75 mm², 24 - 20 AWG 0,25 - 0,75 mm², 24 - 20 AWG
Torque setting with screw terminals 0,25 Nm 0,25 Nm
Stripping length with screw termin-
als
7 mm 7 mm
Conductor cross section with
spring-loaded terminals
1 core flexible without crimp
connector 0,25 - 1,50 mm², 24 - 16 AWG 0,25 - 1,50 mm², 24 - 16 AWG
1 core flexible with crimp con-
nector
0,25 - 0,75 mm², 24 - 20 AWG 0,25 - 0,75 mm², 24 - 20 AWG
Spring-loaded terminals: Terminal
points per connection
1 1
Stripping length with spring-loaded
terminals
9 mm 9 mm
Dimensions
Height 94,0 mm 94,0 mm
Width 22,5 mm 22,5 mm
Depth 121,0 mm 121,0 mm
Weight 129 g 135 g
Where standards are undated, the 2010-07 latest editions shall apply.