Datasheet

PNOZmulti products
Base units
PNOZ m3p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
140
Installation
Dimensions
94 (3.70")
121 (4.76")
135 (5.31")
Commissioning
General wiring guidelines
The wiring is defined in the circuit diagram in the Configurator. There you can select the in-
puts that are to perform a safety function and the outputs that are to switch this safety func-
tion.
Please note:
} Information given in the Technical details [
145] must be followed.
} Outputs:
O0 to O5 are safety outputs
O4 and O5 are relay outputs
O0 to O3 are semiconductor outputs
OA0 is an output to delete a project from the base unit (see online help for the
PNOZmutli Configurator).
} To prevent contact welding, a fuse should be connected before the output contacts (see
technical details).
} Use copper wiring with a temperature stability of 75°C.
} Sufficient fuse protection must be provided on all output contacts with inductive loads.
} The control system and input circuits must always be supplied by a single power sup-
ply. The power supply must meet the regulations for extra low voltages with protective
separation.