Safety characteristic data
Unit Operating
mode
EN ISO
13849-1: 2008
PL
EN ISO
13849-1: 2008
Category
EN 62061
SIL CL
EN 62061
PFH
D
[1/h]
EN ISO
13849-1: 2008
T
M
[year]
Logic
CPU 2-channel PL e Cat. 4 SIL CL 3 4,90E-09 20
Expansion PL e Cat. 4 SIL CL 3 9,20E-09 20
Input
SC inputs 1-channel PL d Cat. 2 SIL CL 2 2,50E-09 20
SC inputs 2-channel PL e Cat. 4 SIL CL 3 2,90E-10 20
SC inputs Short circuit-
forming
safety mats
PL d Cat. 3 SIL CL 2 1,81E-09 20
SC inputs 1-ch., pulsed
light barrier
PL e Cat. 4 SIL CL 3 2,50E-10 20
Cascad. in-
puts
PL e Cat. 4 SIL CL 3 3,10E-10 20
Output
SC outputs 1-channel PL d Cat. 2 SIL CL 2 7,00E-09 20
SC outputs 2-channel PL e Cat. 4 SIL CL 3 8,60E-10 20
Cascad. out-
puts
PL e Cat. 4 SIL CL 3 4,91E-10 20
Relay outputs 1-channel PL c Cat. 1 - 2,90E-08 20
Relay outputs 2-channel PL e Cat. 4 SIL CL 3 3,00E-10 20
All the units used within a safety function must be considered when calculating the safety
characteristic data.
The PFH value depends on the switching frequency and the load on the relay output.
If the service life graphs are not accessible, the stated PFH value can be used irrespective
of the switching frequency and the load, as the PFH value already considers the relay's
B10d value as well as the failure rates of the other components.