Datasheet

PNOZmulti 2 products
Motion monitoring modules
PNOZ m EF 1MM
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
753
pnp proximity switch with resistor R = 10 kOhm
npn proximity switch with resistor R = 47 kOhm
Connection of an encoder
Proceed as follows when connecting the encoder:
} The encoder can be connected via an adapter (e.g. ) or directly to the PNOZ m EF
1MM.
} Use only shielded cables for all connections. Please refer to the chapter entitled "EMC-
compliant wiring".
} Always connect GND on the encoder to GND on the connector.
} If the encoder signals are not terminated with 120 Ohm in the frequency converter or
adapter cable longer than 5 metres is used, the encoder signals must be terminated
with Z
0
= 120 Ohm between A and /A, B and /B, Z and /Z.