Datasheet

PNOZmulti Mini products
Fieldbus modules
PNOZ mmc4p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
620
Termination DeviceNet
To minimise cable reflection and to guarantee a defined rest signal on the transmission line,
DeviceNetmust be terminated at both ends.
Setting the transmission rate
Set the transmission rate using DIP switches S1 and S2 (DR).
Transmission rate DIP switch
S1 S2
125 kBit/s Off Off
250 kBit/s On Off
500 kBit/s Off On
--- On On
Setting the station address
The station address of the expansion module PNOZ mmc4p is set from 0 ... 63 (binary) us-
ing DIP switches 1 to 32.
Station address DIP switch
32 16 8 4 2 1
0 Off Off Off Off Off Off
1 Off Off Off Off Off On
2 Off Off Off Off On Off
3 Off Off Off Off On On
... ... ... ... ... ... ...
62 On On On On On Off
63 On On On On On On
Download modified project to the PNOZmulti safety system
As soon as an additional expansion module has been connected to the system, the project
must be amended using the PNOZmulti Configurator. Proceed as described in the operat-
ing instructions for the base unit.