Datasheet

PNOZmulti 2 products
Fieldbus modules
PNOZ m ES CC-Link
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
898
} External measures must be used to connect the terminal to the functional earth,
when the mounting rail is not connected to the functional earth.
} Always connect the mounting rail to the protective earth via an earthing terminal. This
will be used to dissipate hazardous voltages in the case of a fault.
} The power supply must meet the regulations for extra low voltages with protective sep-
aration.
Connecting the supply voltage
Connect the supply voltage to the fieldbus module:
} 24 V terminal: + 24 VDC
} 0 V terminal: 0 V
} Protect the supply voltage as follows:
Circuit breaker, characteristic C - 6 A
or
Blow-out fuse, slow, 6A
Interface assignment
It is possible to define which outputs on the safety system will communicate with CC-Link.
The connection to CC-Link is made via a 5-pin screw connector.
1 2 3 4 5
DA FG/
PE
DB DG SLD
DA
FG/PE
DB
DG
SLD
1: DA (Channel A)
2: DB (Channel B)
3: DG (Earth)
4: SLD (Cable shield)
5: FG/PE (Functional earth)