Commissioning
General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Please note:
} Information given in the Technical details [
199] must be followed.
} Use copper wire that can withstand 75°C.
} Two connection terminals are available for each of the supply connections 24 V and 0 V
(semiconductor outputs), plus A1 and A2 (power supply). This means that the supply
voltage can be looped through several connections. When the supply voltage is looped,
the current at each terminal may not exceed 3A.
} Please note: The supply voltage always must be present at X2, even if you do not use
the semiconductor outputs.
The unit has 2 dual-pole semiconductor outputs. These may be configured as single-pole or
redundant outputs. The output assignment is defined in the PNOZmulti Configurator. Wire
the output circuit as described in the table.
Connection
Supply voltage AC DC
24 V
+ 24 V DC
0 V
0 V