Datasheet

Relays for functional safety
Safety relays PNOZsigma
PNOZ s7.2
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
736
Relay outputs 750177 751177
Utilisation category of auxiliary con-
tacts
AC1 at 240 V 240 V
Min. current 0,01 A 0,01 A
Max. current 2 A 2 A
Max. power 500 VA 500 VA
DC1 at 24 V 24 V
Min. current 0,01 A 0,01 A
Max. current 2 A 2 A
Max. power 50 W 50 W
Utilisation category
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Utilisation category of safety con-
tacts
AC15 at 230 V 230 V
Max. current 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V
Max. current 5 A 5 A
Utilisation category of auxiliary con-
tacts
AC15 at 230 V 230 V
Max. current 2 A 2 A
DC13 (6 cycles/min) at 24 V 24 V
Max. current 2 A 2 A
Utilisation category in accordance
with UL
Voltage 240 V AC G.U. (same polarity) 240 V AC G.U. (same polarity)
With current 6 A 6 A
Voltage 24 V DC G. U. 24 V DC G. U.
With current 6 A 6 A
External contact fuse protection,
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Max. melting integral 260 A²s 260 A²s
Blow-out fuse, quick 10 A 10 A
Blow-out fuse, slow 6 A 6 A
Blow-out fuse, gG 10 A 10 A
Circuit breaker 24V AC/DC,
characteristic B/C 6 A 6 A