Datasheet

Relays for functional safety
Safety relays PNOZsigma
PNOZ s6
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
679
Cycles x 1000
Switching current (A)
Fig.: Service life graphs at 110 VDC
Example
} Inductive load: 0.2 A
} Utilisation category: AC15
} Contact service life: 2 000 000 cycles
Provided the application to be implemented requires fewer than 2 000 000 cycles, the PFH
value (see Technical details [ 667]) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With DC con-