Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ X2.8P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
105
Conventional thermal current
while loading several contacts
787301 787302
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 6 A 6 A
Conv. therm. current with 2 con-
tacts 4 A 6 A
Conv. therm. current with 3 con-
tacts 3,5 A 4,5 A
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 6 A 6 A
Conv. therm. current with 2 con-
tacts 6 A 6 A
Conv. therm. current with 3 con-
tacts 5 A 4,5 A
Times 787301 787302
Switch-on delay
With automatic start typ. 250 ms 340 ms
With automatic start max. 450 ms 400 ms
With automatic start after power
on typ. 250 ms 600 ms
With automatic start after power
on max. 450 ms 800 ms
With manual start typ. 125 ms 180 ms
With manual start max. 450 ms 400 ms
Delay-on de-energisation
With E-STOP typ. 15 ms 10 ms
With E-STOP max. 30 ms 20 ms
With power failure typ. 60 ms
With power failure max. 100 ms
With power failure typ. UB 240 V 1100 ms
With power failure max. UB 240
V 1500 ms
With power failure typ. UB 24 V 180 ms
With power failure max. UB 24 V 230 ms
Recovery time at max. switching
frequency 1/s
After E-STOP 50 ms 50 ms
After power failure 200 ms 1500 ms
Supply interruption before de-ener-
gisation 20 ms 20 ms
Simultaneity, channel 1 and 2 max.