Datasheet

Relays for functional safety
Safety relays PNOZsigma
PNOZ s30
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
841
EMC-compliant wiring for connecting 2 proximity switches
PNOZ s30
IN1
IN2
RJ45
GND
To avoid EMC interference we recommend that the shield on the sensor cables or the
housing of the shielded junction box is only connected to earth at a single point:
A or B or C or D or E
Conductor loops outside the shield must be avoided.
If a shielded junction box is not used, the shield must run continuously from the sensor to
the evaluation device.