Datasheet

Relays for functional safety
Safety relays PNOZsigma
PNOZ s7
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
709
Relay outputs 750107 751107 751187
Utilisation category of
safety contacts
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 6 A 6 A 6 A
Max. power 1500 VA 1500 VA 1500 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 6 A 6 A 6 A
Max. power 150 W 150 W 150 W
Utilisation category of
auxiliary contacts
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 2 A 2 A 2 A
Max. power 500 VA 500 VA 500 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 2 A 2 A 2 A
Max. power 50 W 50 W 50 W
Utilisation category
In accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Utilisation category of
safety contacts
AC15 at 230 V 230 V 230 V
Max. current 5 A 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 5 A 5 A 5 A
Utilisation category of
auxiliary contacts
AC15 at 230 V 230 V 230 V
Max. current 2 A 2 A 2 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 2 A 2 A 2 A
Utilisation category in ac-
cordance with UL
Voltage
240 V AC G.U. (same po-
larity)
240 V AC G.U. (same po-
larity)
240 V AC G.U. (same po-
larity)
With current 6 A 6 A 6 A
Voltage 24 V DC G. U. 24 V DC G. U. 24 V DC G. U.
With current 6 A 6 A 6 A