Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ XV2.1P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
328
Relay outputs 777540 777542 777544
External contact fuse pro-
tection, delayed safety
contacts
Max. melting integral 240 A²s 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A 10 A
Blow-out fuse, slow 6 A 6 A 6 A
Blow-out fuse, gG 10 A 10 A 10 A
Circuit breaker 24 V
AC/DC, characteristic
B/C 6 A 6 A 6 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal
current while loading
several contacts
777540 777542 777544
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 8 A 8 A 8 A
Conv. therm. current
with 2 contacts 7 A 7 A 7 A
Conv. therm. current
with 3 contacts 5,7 A 5,7 A 5,7 A
Conv. therm. current
with 4 contacts 5 A 5 A 5 A
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 8 A 8 A 8 A
Conv. therm. current
with 2 contacts 7 A 7 A 7 A
Conv. therm. current
with 3 contacts 5,7 A 5,7 A 5,7 A
Conv. therm. current
with 4 contacts 5 A 5 A 5 A