Relay outputs 777303 777307
Utilisation category in accordance
with UL
Voltage 240 V AC G. P. 240 V AC G. P.
With current 6 A 6 A
Voltage 24 V DC Resistive 24 V DC Resistive
With current 6 A 6 A
Pilot Duty C300, R300 B300, R300
External contact fuse protection,
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Max. melting integral 240 A²s 100 A²s
Blow-out fuse, quick 6 A 6 A
Blow-out fuse, slow 4 A 4 A
Blow-out fuse, gG 6 A 6 A
Circuit breaker 24V AC/DC,
characteristic B/C 4 A 4 A
Conventional thermal current 6 A 6 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Times 777303 777307
Switch-on delay
With automatic start typ. 60 ms 120 ms
With automatic start max. 90 ms 150 ms
With automatic start after power
on typ. 60 ms 130 ms
With automatic start after power
on max. 100 ms 160 ms
With manual start typ. 40 ms 40 ms
With manual start max. 90 ms 150 ms
With monitored start typ. 35 ms 35 ms
With monitored start max. 50 ms 50 ms
Delay-on de-energisation
With E-STOP typ. 15 ms 15 ms
With E-STOP max. 30 ms 30 ms
With power failure typ. 70 ms 40 ms
With power failure max. 110 ms 70 ms
With power failure typ. UB 240 V 320 ms
With power failure max. UB 240
V 500 ms
Recovery time at max. switching
frequency 1/s
After E-STOP 50 ms 50 ms
After power failure 150 ms 550 ms