Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ XV2P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
312
Relay outputs 787503 787504
External contact fuse protection,
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Max. melting integral 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A
Blow-out fuse, slow 6 A 6 A
Blow-out fuse, gG 10 A 10 A
Circuit breaker 24V AC/DC,
characteristic B/C 6 A 6 A
External contact fuse protection,
delayed safety contacts
Max. melting integral 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A
Blow-out fuse, slow 6 A 6 A
Blow-out fuse, gG 10 A 10 A
Circuit breaker 24 V AC/DC,
characteristic B/C 6 A 6 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal current
while loading several contacts
787503 787504
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 8 A 8 A
Conv. therm. current with 2 con-
tacts 7 A 7 A
Conv. therm. current with 3 con-
tacts 5,7 A 5,7 A
Conv. therm. current with 4 con-
tacts 5 A 5 A
Times 787503 787504
Switch-on delay
With automatic start typ. 350 ms 350 ms
With automatic start max. 650 ms 650 ms
With automatic start after power
on typ. 385 ms 385 ms
With automatic start after power
on max. 700 ms 700 ms
With monitored start typ. 35 ms 35 ms
With monitored start max. 70 ms 70 ms