Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ XV2P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
302
Conventional thermal
current while loading
several contacts
777500 777502 777503
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 8 A 8 A 8 A
Conv. therm. current
with 2 contacts 7 A 7 A 7 A
Conv. therm. current
with 3 contacts 5,7 A 5,7 A 5,7 A
Conv. therm. current
with 4 contacts 5 A 5 A 5 A
Times 777500 777502 777503
Switch-on delay
With automatic start
typ. 350 ms 350 ms 350 ms
With automatic start
max. 650 ms 650 ms 650 ms
With automatic start
after power on typ. 385 ms 385 ms 385 ms
With automatic start
after power on max. 700 ms 700 ms 700 ms
With monitored start
typ. 35 ms 35 ms 35 ms
With monitored start
max. 70 ms 70 ms 70 ms
Delay-on de-energisation
With E-STOP typ. 15 ms 15 ms 15 ms
With E-STOP max. 30 ms 30 ms 30 ms
With power failure typ. 85 ms 85 ms 85 ms
With power failure max. 200 ms 200 ms 200 ms
Recovery time at max.
switching frequency 1/s
After E-STOP 50 ms +tv 50 ms +tv 50 ms +tv
After power failure 250 ms 250 ms 250 ms
Delay time tv 0,1 s, 0,5 s, 1 s, 2 s, 4 s,
6 s, 8 s, 10 s, 15 s, 20 s,
25 s, 30 s
0,1 s, 0,2 s, 0,3 s, 0,4 s,
0,5 s, 0,6 s, 0,7 s, 0,8 s, 1
s, 1,5 s, 2 s, 3 s 1 s
Time accuracy -15 %/+15 % +50 ms -15 %/+15 % +50 ms -15 %/+15 % +50 ms
Repetition accuracy 2 % 2 % 2 %
Waiting period with a
monitored start 300 ms 300 ms 300 ms
Min. start pulse duration
with a monitored start 30 ms 30 ms 30 ms