Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ X11P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
272
Service life graph
The service life graphs indicate the number of cycles from which failures due to wear must
be expected. The wear is mainly caused by the electrical load; the mechanical load is negli-
gible.
Number of cycles x 1000
Switching current (A)
Example
} Inductive load: 0.2 A
} Utilisation category: AC15
} Contact service life: 4 000 000 cycles
Provided the application to be implemented requires fewer than 4 000 000 cycles, the PFH
value (see Technical details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With DC con-
tactors, use flywheel diodes for spark suppression.
Order reference
Product type Features Connection type Order no.
PNOZ X11P 24 VAC; 24 VDC Screw terminals 777 080
PNOZ X11P C 24 VAC; 24 VDC Spring-loaded terminals 787 080
PNOZ X11P 110 - 120 VAC; 24 VDC Screw terminals 777 083
PNOZ X11P C 110 - 120 VAC; 24 VDC Spring-loaded terminals 787 083
PNOZ X11P 230 - 240 VAC; 24 VDC Screw terminals 777 086
PNOZ X11P C 230 - 240 VAC; 24 VDC Spring-loaded terminals 787 086