232
Times 777607 777609 787609
Delay-on de-energisation
With E-STOP typ. 20 ms 20 ms 20 ms
With E-STOP max. 30 ms 30 ms 30 ms
With power failure typ. 60 ms 170 ms 170 ms
With power failure max. 80 ms 250 ms 250 ms
Recovery time at max.
switching frequency 1/s
After E-STOP 50 ms 50 ms 50 ms
After power failure 100 ms 300 ms 300 ms
Min. start pulse duration
with a monitored start 30 ms 50 ms 50 ms
Supply interruption before
de-energisation 20 ms 20 ms 20 ms
Environmental data 777607 777609 787609
Climatic suitability EN 60068-2-78 EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C -10 - 55 °C -10 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during op-
eration Not permitted Not permitted Not permitted
EMC EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
Vibration
In accordance with the
standard EN 60068-2-6 EN 60068-2-6 EN 60068-2-6
Frequency 10 - 55 Hz 10 - 55 Hz 10 - 55 Hz
Amplitude 0,35 mm 0,35 mm 0,35 mm
Airgap creepage
In accordance with the
standard EN 60947-1 EN 60947-1 EN 60947-1
Overvoltage category III / II III / II III / II
Pollution degree 2 2 2
Rated insulation voltage 250 V 250 V 250 V
Rated impulse withstand
voltage 4 kV 4 kV 4 kV
Protection type
Mounting area (e.g.
control cabinet) IP54 IP54 IP54
Housing IP40 IP40 IP40
Terminals IP20 IP20 IP20