Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ X9P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
231
Relay outputs 777607 777609 787609
External contact fuse pro-
tection, auxiliary contacts
Max. melting integral 240 A²s 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A 10 A
Blow-out fuse, slow 6 A 6 A 6 A
Blow-out fuse, gG 10 A 10 A 10 A
Circuit breaker 24 V
AC/DC, characteristic
B/C 6 A 6 A 6 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal
current while loading
several contacts
777607 777609 787609
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 8 A 8 A 8 A
Conv. therm. current
with 2 contacts 8 A 8 A 8 A
Conv. therm. current
with 3 contacts 8 A 8 A 8 A
Conv. therm. current
with 4 contacts 7 A 7 A 7 A
Conv. therm. current
with 5 contacts 6 A 6 A 6 A
Conv. therm. current
with 6 contacts 5,5 A 5,5 A 5,5 A
Conv. therm. current
with 7 contacts 5 A 5 A 5 A
Times 777607 777609 787609
Switch-on delay
With automatic start
typ. 130 ms 200 ms 200 ms
With automatic start
max. 200 ms 250 ms 250 ms
With automatic start
after power on typ. 150 ms 220 ms 220 ms
With automatic start
after power on max. 220 ms 300 ms 300 ms
With manual start typ. 150 ms 200 ms 200 ms
With manual start max. 200 ms 250 ms 250 ms
With monitored start
typ. 100 ms 150 ms 150 ms
With monitored start
max. 150 ms 220 ms 220 ms