Datasheet
Relays for functional safety
Safety relays PNOZ X
PNOZ X8P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
182
Semiconductor output supply voltage Y35
} A high signal is present at semi-conductor output Y35 if the supply voltage is present
and the internal fuse has not blown.
Operating modes
} Single-channel operation: No redundancy in the input circuit, earth faults in the start
and input circuit are detected.
} Dual-channel operation with detection of shorts across contacts: Redundant input cir-
cuit, PNOZ X8P detects
– earth faults in the start and input circuit,
– short circuits in the input circuit,
– shorts across contacts in the input circuit.
} Dual-channel operation without detection of shorts across contacts: Redundant input
circuit, detects PNOZ X8P
– earth faults in the start and input circuit,
– short circuits in the input circuit.
} Automatic start: Unit is active once the input circuit has been closed.
} Manual start: Unit is active once the input circuit and the start circuit are closed.
} Monitored start: Unit is active once
– the input circuit is closed and then the start circuit is closed and opened again.
– the start circuit is closed and then opened again once the input circuit is closed.
} Increase in the number of available contacts by connecting contact expander modules
or external contactors/relays.