Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ X8P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
181
Types: AC
} U
B
: 24 VAC; Order no. 777770, 787770
} U
B
: 110 VAC; Order no. 777764, 787764
} U
B
: 115 VAC; Order no. 777765
} U
B
: 120 VAC; Order no. 777766, 787766
} U
B
: 230 VAC; Order no. 777768, 787768
*Insulation between the non-marked area and the relay contacts: Basic insulation (over-
voltage category III), Protective separation (overvoltage category II)
Function Description
The safety relay PNOZ X8P provides a safety-oriented interruption of a safety circuit. When
supply voltage is supplied the "POWER" LED is lit. The unit is ready for operation when the
feedback loop Y1-Y2 and the start circuit S33-S34 are closed. The "START" LED is lit.
} Input circuit is closed (e.g. E-STOP pushbutton not operated):
LEDs "CH1 IN" and "CH2 IN" will light.
The "START" LED goes out.
Safety contacts 13-14, 23-24 and 33-34 are closed, auxiliary contacts 41-42 and
51-52 are opened. The unit is active.
LEDs "CH1" and "CH2" will light.
A high signal is present at the semiconductor output switch state Y32.
} Input circuit is opened (e.g. E-STOP pushbutton operated):
LEDs "CH1 IN" and "CH2 IN" go out.
Safety contacts 13-14, 23-24 and 33-34 are opened redundantly, auxiliary contacts
41-42 and 51-52 are closed.
The LEDs "CH1" and "CH2" go out.
A low signal is present at the semiconductor output switch state Y32.