Relays for functional safety
Safety relays PNOZ X
PZE X4VP
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
444
Relay outputs 777583 787580 787581
Utilisation category in ac-
cordance with UL
Voltage
250 V AC G.U. (same po-
larity)
250 V AC G.U. (same po-
larity)
250 V AC G.U. (same po-
larity)
With current 6 A 6 A 6 A
Voltage 24 V DC G. U. 24 V DC G. U. 24 V DC G. U.
With current 6 A 6 A 6 A
Pilot Duty B300, R300 B300, R300 B300, R300
External contact fuse pro-
tection, safety contacts
In accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
External contact fuse pro-
tection, delayed safety
contacts
Max. melting integral 66 A²s 66 A²s 66 A²s
Blow-out fuse, quick 6 A 6 A 6 A
Blow-out fuse, slow 4 A 4 A 4 A
Blow-out fuse, gG 6 A 6 A 6 A
Circuit breaker 24 V
AC/DC, characteristic
B/C 4 A 4 A 4 A
Contact material AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au
Conventional thermal
current while loading
several contacts
777583 787580 787581
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 6 A 6 A 6 A
Conv. therm. current
with 2 contacts 5 A 5 A 5 A
Conv. therm. current
with 3 contacts 4,5 A 4,5 A 4,5 A
Conv. therm. current
with 4 contacts 4 A 4 A 4 A
Times 777583 787580 787581
Switch-on delay
With automatic start
after power on typ. 55 ms 55 ms 55 ms
With automatic start
after power on max. 200 ms 200 ms 200 ms
Delay time tv 3 s 0,5 s 1 s