Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ XV3P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
366
Relay outputs 787510 787512 787518
External contact fuse pro-
tection, safety contacts
In accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Max. melting integral 240 A²s 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A 10 A
Blow-out fuse, slow 6 A 6 A 6 A
Blow-out fuse, gG 10 A 10 A 10 A
Circuit breaker 24V
AC/DC, characteristic
B/C 6 A 6 A 6 A
External contact fuse pro-
tection, delayed safety
contacts
Max. melting integral 240 A²s 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A 10 A
Blow-out fuse, slow 6 A 6 A 6 A
Blow-out fuse, gG 10 A 10 A 10 A
Circuit breaker 24 V
AC/DC, characteristic
B/C 6 A 6 A 6 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal
current while loading
several contacts
787510 787512 787518
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 8 A 8 A 8 A
Conv. therm. current
with 2 contacts 6,8 A 6,8 A 6,8 A
Conv. therm. current
with 3 contacts 5,5 A 5,5 A 5,5 A
Conv. therm. current
with 4 contacts 4,8 A 4,8 A 4,8 A
Conv. therm. current
with 5 contacts 4,3 A 4,3 A 4,3 A