Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ XV3P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
355
Relay outputs 777510 777512 777514
External contact fuse pro-
tection, delayed safety
contacts
Max. melting integral 240 A²s 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A 10 A
Blow-out fuse, slow 6 A 6 A 6 A
Blow-out fuse, gG 10 A 10 A 10 A
Circuit breaker 24 V
AC/DC, characteristic
B/C 6 A 6 A 6 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal
current while loading
several contacts
777510 777512 777514
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 8 A 8 A 8 A
Conv. therm. current
with 2 contacts 6,8 A 6,8 A 6,8 A
Conv. therm. current
with 3 contacts 5,5 A 5,5 A 5,5 A
Conv. therm. current
with 4 contacts 4,8 A 4,8 A 4,8 A
Conv. therm. current
with 5 contacts 4,3 A 4,3 A 4,3 A
Times 777510 777512 777514
Switch-on delay
With automatic start
typ. 350 ms 350 ms 350 ms
With automatic start
max. 650 ms 650 ms 650 ms
With automatic start
after power on typ. 385 ms 385 ms 385 ms
With automatic start
after power on max. 700 ms 700 ms 700 ms
With monitored start
typ. 35 ms 35 ms 35 ms
With monitored start
max. 70 ms 70 ms 70 ms