Datasheet

Relays for functional safety
Safety relays PNOZsigma
PNOZ s10
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
780
Number of cycles x 1000
Switching current (A)
10
0,1 0,5 1 2 3 4 5 6 7 8 910
100
1000
DC 1: 110 V
DC 13: 110 V
10000
Fig.: Service life graphs at 110 V DC
Example
} Inductive load: 2 A
} Utilisation category: AC15
} Contact service life: 300 000 cycles
Provided the application to be implemented requires fewer than 300 000 cycles, the PFH
value (see Technical details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With DC con-
tactors, use flywheel diodes for spark suppression.
Order reference
Product type Features Connection type Order No.
PNOZ s10 24 VDC Screw terminals 750 110
PNOZ s10 C 24 VDC Spring-loaded terminals 751 110