Datasheet

Relays for functional safety
Safety relays PNOZsigma
PNOZ s5
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
639
Reset with start-up test
Legend
} POWER: Supply voltage
} Start: Start circuit
} Input: Input circuits
} Output safe: Safety contacts, instantaneous
} Output safe del: Safety contacts, delayed
} Output semi: Semiconductor output
} t
1
: Switch-on delay
} t
2
: Delay-on de-energisation
} t
v
: Delay time
} t
6
: Recovery time
Installation
Install base unit without contact expansion module:
} Ensure that the plug terminator is inserted at the side of the unit.
Connect base unit and PNOZsigma contact expansion module:
} Remove the plug terminator at the side of the base unit and at the contact expansion
module.
} Connect the base unit and the contact expansion module to the supplied connector be-
fore mounting the units to the DIN rail.
Installation in control cabinet
} The safety relay should be installed in a control cabinet with a protection type of at least
IP54.
} Use the notch on the rear of the unit to attach it to a DIN rail (35mm).
} When installed vertically: Secure the unit by using a fixing element (e.g. retaining
bracket or end angle).
} Push the device upwards or downwards before lifting it from the DIN rail.