Datasheet
Relays for functional safety
Safety relays PNOZsigma
PNOZ s2
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
560
Block diagram/terminal configuration
Interface
expansion
module
Fig.: Centre: Front view with cover, right: Front view without cover
*Safe separation from non-marked area in accordance with EN 60947-1, 6 kV, basic insula-
tion between all safety contacts.
Function description
} Single-channel operation: No redundancy in the input circuit, earth faults in the start
and input circuit are detected.
} Automatic start: Unit is active once the input circuit has been closed.
} Manual start Unit is active once the input circuit and the start circuit are closed.
} Monitored start with falling edge: Unit is active once
– the input circuit is closed and then the start circuit is closed and opened again.
– the start circuit is closed and then opened again once the input circuit is closed.
} Monitored start with rising edge: Unit is active once the input circuit is closed and
once the start circuit is closed after the waiting period has elapsed (seetechnical de-
tails).
} Increase in the number of available instantaneous safety contacts by connecting con-
tact expander modules or external contactors/relays;
A connector can be used to connect 1 PNOZsigma contact expander module.