Datasheet
Relays for functional safety
Safety relays PNOZ X
PNOZ XV3P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
367
Times 787510 787512 787518
Switch-on delay
With automatic start
typ. 350 ms 350 ms 350 ms
With automatic start
max. 650 ms 650 ms 650 ms
With automatic start
after power on typ. 385 ms 385 ms 385 ms
With automatic start
after power on max. 700 ms 700 ms 700 ms
With monitored start
typ. 35 ms 35 ms 35 ms
With monitored start
max. 70 ms 70 ms 70 ms
Delay-on de-energisation
With E-STOP typ. 15 ms 15 ms 15 ms
With E-STOP max. 30 ms 30 ms 30 ms
With power failure typ. 85 ms 85 ms 85 ms
With power failure max. 200 ms 200 ms 200 ms
Recovery time at max.
switching frequency 1/s
After E-STOP 50 ms +tv 50 ms +tv 50 ms +tv
After power failure 250 ms 250 ms 250 ms
Delay time tv 0,1 s, 0,5 s, 1 s, 2 s, 4 s,
6 s, 8 s, 10 s, 15 s, 20 s,
25 s, 30 s
0,1 s, 0,2 s, 0,3 s, 0,4 s,
0,5 s, 0,6 s, 0,7 s, 0,8 s, 1
s, 1,5 s, 2 s, 3 s
0,3 s, 5 s, 10 s, 20 s, 40
s, 60 s, 80 s, 100 s, 150
s, 200 s, 250 s, 300 s
Time accuracy -15 %/+15 % +50 ms -15 %/+15 % +50 ms -15 %/+15 % +50 ms
Repetition accuracy 2 % 2 % 2 %
Waiting period with a
monitored start 300 ms 300 ms 300 ms
Min. start pulse duration
with a monitored start 30 ms 30 ms 30 ms
Supply interruption before
de-energisation 20 ms 20 ms 20 ms
Simultaneity, channel 1
and 2 max. ∞ ∞ ∞
Environmental data 787510 787512 787518
Climatic suitability EN 60068-2-78 EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C -10 - 55 °C -10 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C 93 % r. h. at 40 °C