Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ X10.11P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
247
Times 777750 787750
Switch-on delay
With automatic start typ. 200 ms 200 ms
With automatic start max. 250 ms 250 ms
With automatic start after power
on typ. 220 ms 220 ms
With automatic start after power
on max. 300 ms 300 ms
With manual start typ. 200 ms 200 ms
With manual start max. 250 ms 250 ms
With monitored start typ. 220 ms 220 ms
With monitored start max. 260 ms 260 ms
Delay-on de-energisation
With E-STOP typ. 20 ms 20 ms
With E-STOP max. 30 ms 30 ms
With power failure typ. 360 ms 360 ms
With power failure max. 480 ms 480 ms
Recovery time at max. switching
frequency 1/s
After E-STOP 50 ms 50 ms
After power failure 500 ms 500 ms
Min. start pulse duration with a
monitored start 50 ms 50 ms
Supply interruption before de-ener-
gisation 150 ms 150 ms
Environmental data 777750 787750
Climatic suitability EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C -10 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during operation Not permitted Not permitted
EMC EN 60947-5-1, EN 61000-6-2, EN
61326-3-1
EN 60947-5-1, EN 61000-6-2, EN
61326-3-1
Vibration
In accordance with the standard EN 60068-2-6 EN 60068-2-6
Frequency 10 - 55 Hz 10 - 55 Hz
Amplitude 0,35 mm 0,35 mm